1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 158/192
Proportional speed control FA01 = 4
Proportional band for condenser fan control in heat pump
To set the temperature/pressure differential between the minimum and the
maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 1
Proportional speed control FA01 = 4
CUT-OFF differential in heat pump. To set a temperature/pressure differential
to stop the fan.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 2
Over ride CUT- OFF in Heat pump. To set a temperature/pressure differential
to keep the minimum fan speed.
Night speed in Heat pump. To set the maximum fan speed percentage value
(30..100%), it is related to the fan power supply.
ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
ON/OFF regulation FA01 = 2/3
SETpoint step n° 4
ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
ON/OFF regulation FA01 = 2/3
SETpoint step n° 4
Pre ventilation in Heat Pump
(only if FA01 = 4 )
Post ventilation in Heat Pump
Outside temperature to enable post ventilation in Heat Pump
Condenser fan speed during post ventilation
Condenser fan max modulation speed in defrost
Temp/press to force condenser fan max speed in defrost
Anti-freeze heaters/integration heating setpoint for air/air unit in Chiller mode.
To set a temperature value, below this value the anti-freeze relay is activated.
Regulation band for antifreeze in Chiller mode.
Set Anti-freeze heaters/integration heating setpoint for air/air unit in HP mode.
To set a temperature value, below this value the anti-freeze relay is activated.
Regulation band for antifreeze in HP mode.
Antifreeze heaters / integration heating in defrost
0= ON only with thermoregulation control
1= ON with thermoregulation and during the defrosting cycle
Antifreeze probe to manage heaters / support heaters in Chiller mode.
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
4= External temperature
Antifreeze probe to manage heaters / support heaters in HP mode.
0= Not enabled
1= Evaporator inlet.
2= Evaporator outlet 1 and 2.
3= Evaporator outlet 1 and 2 and common outlet
4= External temperature