1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 158/192
FA 20
Proportional speed control FA01 = 4
Proportional band for condenser fan control in heat pump
To set the temperature/pressure differential between the minimum and the
maximum of the fan speed regulation.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 1
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 21
Proportional speed control FA01 = 4
CUT-OFF differential in heat pump. To set a temperature/pressure differential
to stop the fan.
ON/OFF regulation FA01 = 2/3
Differential step circuit n° 2
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 22
Over ride CUT- OFF in Heat pump. To set a temperature/pressure differential
to keep the minimum fan speed.
0.1
0
0.1
1
25.0
45
14.0
203
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 23
Night speed in Heat pump. To set the maximum fan speed percentage value
(30..100%), it is related to the fan power supply.
0
100
%
FA 24
Hot start setpoint
-50.0
-58
110.0
230
°C
°F
Dec
int
FA 25
Hot start differential
0.1
0
25.0
45
°C
°F
Dec
int
FA 26
ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 27
ON/OFF regulation FA01 = 2/3
SETpoint step n° 4
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 28
ON/OFF regulation FA01 = 2/3
SETpoint step n° 3
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 29
ON/OFF regulation FA01 = 2/3
SETpoint step n° 4
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
FA 30
Pre ventilation in Heat Pump
(only if FA01 = 4 )
0
250
Sec
Sec
FA 31
Post ventilation in Heat Pump
0
250
Sec
10Sec
FA 32
Outside temperature to enable post ventilation in Heat Pump
-50.0
-58
110.0
230
°C
°F
Dec
int
FA 33
Condenser fan speed during post ventilation
0
100
%
Condenser fan in defrost
FA 34
Condenser fan max modulation speed in defrost
0
100
%
FA 35
Temp/press to force condenser fan max speed in defrost
-50.0
-58
0.0
0
110.0
230
50.0
725
°C
°F
Bar
Psi
Dec
int
Dec
int
Parameter
Description
min
max
M. u.
Resolution
Ar 1
Anti-freeze heaters/integration heating setpoint for air/air unit in Chiller mode.
To set a temperature value, below this value the anti-freeze relay is activated.
-50.0
-58
110.0
230
°C
°F
Dec
int
Ar 2
Regulation band for antifreeze in Chiller mode.
0.1
0
25.0
45
°C
°F
Dec
Int
Ar 3
Set Anti-freeze heaters/integration heating setpoint for air/air unit in HP mode.
To set a temperature value, below this value the anti-freeze relay is activated.
-50.0
-58
110.0
230
°C
°F
Dec
int
Ar 4
Regulation band for antifreeze in HP mode.
0.1
0
25.0
45
°C
°F
Dec
int
Ar 5
Antifreeze heaters / integration heating in defrost
0= ON only with thermoregulation control
1= ON with thermoregulation and during the defrosting cycle
0
1
Ar 6
Antifreeze probe to manage heaters / support heaters in Chiller mode.
0= Not enabled
1= Evaporator inlet
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
4= External temperature
0
4
Ar 7
Antifreeze probe to manage heaters / support heaters in HP mode.
0= Not enabled
1= Evaporator inlet.
2= Evaporator outlet 1 and 2.
3= Evaporator outlet 1 and 2 and common outlet
4= External temperature
0
4