1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 16/192
1. Push the SET + DOWN keys together for 3 seconds. The top display shows PAS while the bottom
display shows Pr1 labels.
2. Push UP key for 2 seconds and the top display will show Pr2.
1. Push UP key again for 2 seconds and the top display will show Pr3
3. Push SET key and the top display shows a blinking 0, with UP or DOWN insert the Pr3 password. Push
SET and, if the value is correct, top display will show the first family of parameters “ALL”. Otherwise set
the password again.
4. Select a parameter family with DOWN or UP keys.
5. Push SET to enter, the bottom display shows the first available parameter label while the top display
shows its value.
The user can shows and modify all the paramters belonging to this family.
Parameter status, leds and bottom display in Pr3
Leds 1 / 2 are blinking: the parameter can not be changed.
All the leds are off: the parameter is available only in Pr3.
Led 4 on: the parameter can be changed also in Pr2.
Led 4 blinking: the parameter is visible also in Pr2 .
Leds 3 / 4 on: the parameter is available in Pr2 and in Pr1.
Leds 3 / 4 blinking: the parameter is visible in Pr1 and in Pr2.
The MENU key allows to exit from a family to reselect another without exit the Pr2 level.
The MENU key allows to pass to Pr1 starting from a family label.
To exit completely the programming push SET + UP.
How to change a parameter value 6.2.6
Enter the programming
1. Push the SET + DOWN keys together for 3 seconds;
2. Select the parameter label with up and down keys;
3. Push SET to enter the parameter value;
4. Change the value with UP or DOWN keys;
5. Push SET to confirm, after some seconds the display shows the next parameter;
6. Exit: Push SET + UP together when a parameter label is displayed or wait 15seconds without pushing a
key.
NOTE: a new parameter value is confirmed also after the 15 seconds of timeout is expired (without pushing
SET key to confirm).
Change the Password value
6.2.7
Pr1 LEVEL
1) Enter Pr1 visibility level
2) Select a whatever parameter family.
3) Search Pr1 label; push SET key to change the value that now is blinking.
4) Use the UP or DOWN key to insert the NEW PASSWORD value, then push SET to confirm the new
value.
5) Top display blinks for some seconds and then shows the next parameter.
6) Exit the programming pushing SET + UP together or wait the timeout.