1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 167/192
Maximum number of high water temperature alarm events
Always manual reset if AL59 = 0
Always automatic reset if AL59 =16
From automatic to manual reset if AL59 =1..15
High water temperature alarm delay time from ON compressor
Set point higt water temperature
Differential higt water temperature
Analogue input configuration.Allows to select which probe value NTC/PTC
(Pb1..Pb10)
Domestic hot water flow switch alarm delay
San. water flow switch delay to stop pump
Domestic hot water flow switch activation time
San. water flow switch de-activation time
Solar panel flow switch alarm delay
Solar panel flow switch delay to stop pump
Solar panel flow switch activation time
Solar panel flow switch de-activation time
Max. number per hour domestic hot water heaters overload alarm
Always manual if AL73 = 0
Always automatic if AL73 =16
If 16>AL73>0:
automatic if number of alarm < AL73
manual if number of alarm = AL73
Password request to reset manual antifreeze alarm
0= password requested
1= password not requested
Max. number per hour domestic hot water pump overload
Always manual if AL75 = 0
Always automatic if AL75 =16
If 16>AL75>0:
automatic if number of alarm < AL75
manual if number of alarm = AL75
Compressor oil level alarm only signalling
0= automatic / manual reset oil alarm (see AL13) and compressor switch off
1= oil alarm signal only (compressor stays ON)
Compressor overload alarm operation mode
0= always manual reset
1= always automatic reset
Dt temperature to generate compressor/circuit differential oil alarm
Differential to reset compressor/circuit differential oil alarm
Max. number per hour compressor/circuit differential oil alarm
Always manual if AL80 = 0
Always automatic if AL80 =16
If 16>AL80>0:
automatic if number of alarm < AL80
manual if number of alarm = AL80
Compressor/circuit differential oil alarm operation mode
0= disabled
1= enabled for pistons compressors
2= enabled for screw compressors
By pass time of the FC flow switch alarm starting from water pump activation
FC flow switch time activation before blocking FC water pump
FC flow switch activation time to generate the alarm and block the
compressor
FC flow switch de-activation time to reset the alarm
Flow switch alarm reset mode
0= Always manual
1= automatic reset after 1 minute
2= automatic reset after 2 minutes
...
250= automatic reset after 250 minutes
Evaporator/domestic hot water flow switch by-pass time during Out1 / Out2
commutation
Number of defrost alarm per hour to generate the manual reset alarm
Condenser antifreeze alarm
Minimum value of the condenser antifreeze alarm set point in chiller