1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 167/192
AL59
Maximum number of high water temperature alarm events
Always manual reset if AL59 = 0
Always automatic reset if AL59 =16
From automatic to manual reset if AL59 =1..15
0
16
AL60
High water temperature alarm delay time from ON compressor
0
250
sec
10 sec
AL61
Set point higt water temperature
-50.0
-58
110
230
°C
°F
Dec
int
AL62
Differential higt water temperature
0.1
0
25.0
45
°C
°F
Dec
int
AL63
Analogue input configuration.Allows to select which probe value NTC/PTC
(Pb1..Pb10)
0
22
AL64
Low pressure alarm delay
0
250
sec
AL65
Domestic hot water flow switch alarm delay
0
250
Sec
AL66
San. water flow switch delay to stop pump
0
250
Sec
AL67
Domestic hot water flow switch activation time
0
250
Sec
AL68
San. water flow switch de-activation time
0
250
Sec
AL69
Solar panel flow switch alarm delay
0
250
Sec
AL70
Solar panel flow switch delay to stop pump
0
250
Sec
AL71
Solar panel flow switch activation time
0
250
Sec
AL72
Solar panel flow switch de-activation time
0
250
Sec
AL73
Max. number per hour domestic hot water heaters overload alarm
Always manual if AL73 = 0
Always automatic if AL73 =16
If 16>AL73>0:
automatic if number of alarm < AL73
manual if number of alarm = AL73
0
16
AL74
Password request to reset manual antifreeze alarm
0= password requested
1= password not requested
0
1
AL75
Max. number per hour domestic hot water pump overload
Always manual if AL75 = 0
Always automatic if AL75 =16
If 16>AL75>0:
automatic if number of alarm < AL75
manual if number of alarm = AL75
0
16
AL76
Compressor oil level alarm only signalling
0= automatic / manual reset oil alarm (see AL13) and compressor switch off
1= oil alarm signal only (compressor stays ON)
0
1
AL77
Compressor overload alarm operation mode
0= always manual reset
1= always automatic reset
0
1
AL78
Dt temperature to generate compressor/circuit differential oil alarm
0.1
1
14.0
203
bar
psi
Dec
int
AL79
Differential to reset compressor/circuit differential oil alarm
0.1
1
14.0
203
bar
psi
Dec
int
AL80
Max. number per hour compressor/circuit differential oil alarm
Always manual if AL80 = 0
Always automatic if AL80 =16
If 16>AL80>0:
automatic if number of alarm < AL80
manual if number of alarm = AL80
0
16
AL81
Compressor/circuit differential oil alarm operation mode
0= disabled
1= enabled for pistons compressors
2= enabled for screw compressors
0
2
AL82
By pass time of the FC flow switch alarm starting from water pump activation
0
250
Sec
AL83
FC flow switch time activation before blocking FC water pump
0
250
Sec
AL84
FC flow switch activation time to generate the alarm and block the
compressor
0
250
Sec
AL85
FC flow switch de-activation time to reset the alarm
0
250
Sec
AL86
Flow switch alarm reset mode
0= Always manual
1= automatic reset after 1 minute
2= automatic reset after 2 minutes
...
250= automatic reset after 250 minutes
0
250
min
AL87
Evaporator/domestic hot water flow switch by-pass time during Out1 / Out2
commutation
0
250
Sec
Defrost alarm
AL88
Number of defrost alarm per hour to generate the manual reset alarm
0
250
Condenser antifreeze alarm
AL89
Minimum value of the condenser antifreeze alarm set point in chiller
-50.0
-58
AL91
°C
°F
Dec
int