Alarm visualization and reset
Pressing o it is possible to visualize the alarms; the alarm status can be:
o Active: the alarm is still active and it is not possible to reset it
o Reset: the alarm is not active and it is possible to reset it
Manual reset of all alarms:
press to reset all the alarms (only the alarms that are not active)
Manual reset procedure:
o press or to select the alarm;
o press to reset the alarm
In case of compressor overload alarm when the password is requested, operate in this way:
press o to select the compressor overload alarm
press
press
press or to insert the password value (parameter AL46)
press to confirm the operation
Alarm log
Pressing or it is possible to read the last 99 alarms.