15.3 CAPACITY STEP CONTROL
CO06 capacity step operation mode.
To select the right operation mode, please read the compressor technical documentation.
CO06 = 0 ON/OFF step
Eg: compressor with 3 capacity step.
* If CO07=2 o CO07=3 (screw compressor) 25% valve is ON if the Ichill is ON and at set poiont reached;
25% valve is OFF if the Ichill is STD-BY or OFF
CO06 = 1 direct action
Eg: compressor with 3 capacity step.
* If CO07=2 o CO07=3 (screw compressor) 25% valve is ON if the Ichill is ON and at set poiont reached;
25% valve is OFF if the Ichill is STD-BY or OFF
CO06 = 2 inverse action
Eg: compressor with 3 capacity step.
* If CO07=2 o CO07=3 (screw compressor) 25% valve is ON if the Ichill is ON and at set poiont reached;
25% valve is OFF if the Ichill is STD-BY or OFF
CO06 = 3 Continuous steps and direct action
Eg: compressor with 3 capacity step.
* If CO07=2 o CO07=3 (screw compressor) 25% valve is ON if the Ichill is ON and at set poiont reached;
25% valve is OFF if the Ichill is STD-BY or OFF
ATTENTION
When working with capacity control in sequential step in direct or reverse modes: if the power requested is
50% and 75% the unit turn on also the step 25% that must be enabled to make run the other two.