1592015610 User manual IC200D EVO GB rel1.0 10.11.2015_rev10 IC200D 94/192
- FS49=0 the compressors are switched on when domestic hot temperature < FS03 (domestic
hot water set point) FS04 (proportional band); all the compressors are switched on with a delay of
CO03 seconds each other
- FS49=1 the proportional band is divided by the number of compressors; at every step
(proportional band/number of compressors) a compressor will be switched on
FS49=0 Example for machine with 3 compressors
FS49=1 Example for machine with 3 compressors
Domestic hot water heaters:
Domestic hot water is produced using mainly the compressors; the domestic hot water heaters are only used
to produce domestic hot water if one or more compressors are not available for regulation (due to an alarm