EasyManua.ls Logo

Emerson Easyheat Warm Tiles - GFCI Protection and Testing; GFCI Operation, Faults, and Testing; Factory Reset Procedure; Resetting Program Schedules

Emerson Easyheat Warm Tiles
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7
gf1
5/2 Day Wake
12
00
Auto
:
AM
Mo
Figure 18
Duringtheabovesteps,theprogramcanbesaved
atanytimebypressingtheNext/Savebuttonfor
two seconds. If no key input is received for 90
seconds,ortheOn/Offbuttonispressedtoother
position,theprogramwillexitthe7Daysetting
mode saving any of the changes.
J. Ground Fault Interrupter (GFCI)
The thermostat has an integral Ground Fault
CircuitInterrupter(GFCI)withEndofLife(EOL)
feature to isolate the heating cable load and to
detect improper operation of the GFCI circuitry.
Test the GFCI circuitry monthly using the following
procedure:
PresstheGFCITESTbuttononcetosimulateafault:
1. If red GFCI light illuminates on the GFCI TEST
button and the “GFI” symbol flashes on the
display (see Figure 18), the circuitry is working as
expectedandhasactivatedtheGFCIprotection
anddisabledthethermostat.PresstheGFCI
RESET button to restore the thermostat to normal
operation.
2. If red GFCI light illuminates and flashes on the
GFCITESTButtonandtheLCDdisplayisblank,the
GFCI circuitry is not functioning properly. If pressing
the GFCI RESET button does not reset the fault,
thenthermostathasreachedEOLandmustbe
replaced with a new thermostat.
IftheGFCItripsandcan’tbereset,turntheOn/
Off button to Off position; there is a possible fault in
theheatingcable.UnderNOcircumstancesshould
the thermostat be bypassed when a fault condition
exists.
K. Power Outage Recovery
Powerinterruptionstothethermostatwillnotaffect
the program settings. However, a power interruption
ofgreaterthanapproximately10minuteswill
require that the clock be reset (see “Setting the
TimeandDay”above).Ofcourse,forextended
power interruptions, the display will remain blank.
L. Sensor Icon
If the thermostat detects a fault with the Floor
Sensor,theSensoriconwillflashontheLCD.
M. Re-set to factory default values for 5/2 Day & 7
Day programs
PressOn/OffbuttontoOffmode,pressandhold
Back/CancelandNext/SaveandDownbuttonsfor
3 seconds. The time schedules will be set to default
values.

Related product manuals