102      Appendix 1  Parameters 
EV2000 Series Universal Variable Speed Drive    User Manual 
Group F9: Enhanced Functional Parameters 
Para.  Name  LCD Display  Setting range  Unit 
Factory 
setting 
Modif.
F9.00 
Control mode is 
bundled to 
frequency 
selector 
FREQ-COM
MAND 
ATTACHING 
Unit’s place of LED: Select the frequency reference selector in 
panel control mode 
0:No bundling 
1:Digital setting 1(set via  ▲ and ▼) 
2:Digital setting 2(set via terminal UP/DN) 
3:Digital setting 3(set via serial port) 
4:Set the reference via VCI 
5:Set the reference via CCI 
6:Set in pulse mode via terminals 
Ten’s place of LED: Select the frequency reference selector in 
terminal control mode 
0: No bundling 
1:Digital setting 1(set via  ▲ and ▼) 
2:Digital setting 2(set via terminal UP/DN) 
3:Digital setting 3(set via serial port) 
4:Set the reference via VCI 
5:Set the reference via CCI 
6:Set in pulse mode via terminals 
Hundred’s place of LED: Select the frequency reference selector 
in serial port control mode 
0: No bundling 
1:Digital setting 1(set via  ▲ and ▼) 
2:Digital setting 2(set via terminal UP/DN) 
3:Digital setting 3(set via serial port) 
4:Set the reference via VCI 
5:Set the reference via CCI 
6:Set in pulse mode via terminals 
1 000 
○ 
F9.01 
Auxiliary 
reference 
channel 
AUX REF 
0:No auxiliary reference frequency; 
1:Digital setting 1, set by  ▲ and ▼(given by F9.03 directly); 
2:Digital setting 2, set by terminal UP/DN (given by F9.03 
directly); 
3:Digital setting 3, set by serial port(given by F9.03 directly); 
4:Set the reference via VCI 
5:Set the reference via CCI 
6:Set in pulse mode via terminals 
4:Set the reference via VCI 
5:Set the reference via CCI 
9:Set in pulse mode via terminals 
10:VCI-5; 
11:CCI-5; 
12:PULSE-0.5×F1.03 
Note: Disabled together with main reference selector frequencies 
in items 4~12 use the setting of F1.00. 
1 0 
○ 
F9.02 
Auxiliary 
reference 
coefficient 
AUX REF 
FACTOR 
0.00~9.99(only for F9.01=4~12)  0.01  1.00 
○ 
F9.03 
Initial auxiliary 
frequency 
AUX FREQ  0.00~650.0Hz  0.01  0.00Hz 
○ 
F9.04 
Auxiliary 
frequency 
control 
AUX FREQ 
CTR 
Unit’s place of LED: Saving control 
0:Saving auxiliary frequency at power off 
1:Not saving auxiliary frequency at power off 
Ten’s place of LED: 
0:Holding auxiliary frequency at stop 
1:Clearing reference frequency at stop 
Hundred’s place of LED: polarities of frequency 
0:Positive       1:Negative 
Note: Only valued at F9.01=1, 2 or 3 
1 000 
○