50      Chapter 5  Parameter Introductions 
EV2000 Series Universal Variable Speed Drive    User Manual 
When the motor operates without load or with light load, 
the drive can adjust its output voltage by detecting the 
load current to achieve the energy-saving effects. 
 Note: 
This function is especially useful for the fan & pump loads. 
F3.06 AVR function 
Range:0. 1. 2【2】
0:disabled 
1: enabled all the time 
2: disabled in Dec process 
AVR means automatic voltage regulation. 
The function can regulate the output voltage and make it 
constant. Therefore, generally AVR function should be 
enabled, especially when the input voltage is higher than 
the rated voltage. 
In Dec-to-stop process, if AVR function is disabled, the 
Dec time is short but the operating current is big. If AVR 
function is enabled all the time, the motor decelerates 
steadily, the operating current is small but the Dec time 
is prolonged. 
F3.07 Gain of slip 
compensation 
Range:0.0~300.0%【100.0%】
F3.08 Limit of slip 
compensation 
Range:0.0~250.0%【200.0%】
F3.09 Compensation 
time constant 
Range:0.1~25.0s【2.0s】 
The motor’s slip changes with the load torque, which 
results in the variance of motor speed. The drive’s 
output frequency can be adjusted automatically through 
slip compensation according to the load torque. 
Therefore the change of speed due to the load change 
is reduced as shown in Fig. 5-18. 
100%
Motor's 
load
Slip
Positive slip 
compensation
-100%
Negative slip 
compensation
 
Fig. 5-18 Auto slip compensation 
Motoring status: Increase the gain of slip compensation 
gradually when the actual speed is lower than the 
reference speed (F3.07). 
Regenerating status: Increase the gain of slip 
compensation gradually when the actual speed is higher 
than the reference speed (F3.07). 
Range of slip compensation: limit of slip 
compensation(F3.08) 
× rated slip(FH.08) 
 Note: 
The value of automatically compensated slip is dependent 
on the motor’s rated slip, therefore the motor’s rated slip 
must be set correctly (FH.08). 
F3.10 Carrier wave 
frequency 
Range:0.7~15.0kHz【depend on 
drive model】 
Table 5-3 Drive’s type and carrier wave frequency (CWF) 
        CWF 
Type 
Highest 
(kHz) 
Lowest 
(kHz) 
Factory 
setting (kHz)
Type G:5.5kW~45kW 
Type P:7.5kW~55kW 
15 3  8 
Type G:55kW~90kW 
Type P:75kW~110kW 
10 1  3 
Type G:110kW~220kW
Type P:132kW~280kW
6 0.7  2 
Table 5-4  CWF characteristics 
CWF  Decrease  Increase 
Motor’s noise 
↑  ↓ 
Leakage current 
↓  ↑ 
Disturbance 
↓  ↑ 
 Notes: 
In order to achieve better control performances, the ratio of 
carrier frequency to the maximum operating frequency of 
the drive should not be less than 36. 
F3.11 Auto adjusting of CWF 
Range:0. 1【1】 
0: disabled 
1: enabled 
When this function is enabled, the drive can adjust the 
CWF automatically according to the internal temperature 
of the drive. At this time, the drive’s actual Max CWF is 
restricted by F3.10. 
F3.12 Motor tone adjustment 
Range:0~10【0】 
F3.12 can be used to adjust the motor’s tone, and is 
only effective for the CWF below 6kHz. 
If this parameter is set to 0, the function is disabled. 
F3.13 Jog operating 
frequency 
Range:0.10~50.00Hz
【5.00Hz】 
F3.14 Interval of Jog 
operation  
Range:0.0~100.0s【0.0s】
F3.15 Acc time of Jog 
operation  
Range:0.1~60.0s
【6.0s/20.0s】 
F3.16 Dec time of Jog 
operation 
Range:0.1~60.0s
【6.0s/20.0s】