54      Chapter 5  Parameter Introductions 
EV2000 Series Universal Variable Speed Drive    User Manual 
Thousand’s place: time unit 
0: Second 
1: Minute 
This unit is only valid for defining the PLC operating time. 
The unit of Acc/Dec time in PLC operation is determined 
by F9.09. 
 Note: 
1. The stage is ineffective if the time of this stage of PLC 
operation is set to 0. 
2. You can use terminals to pause and disable PLC 
operation, and clear the memorized parameters. See the 
introductions to group F7 parameters. 
F4.01 Stage 1 setting 
Range: 000~323【000】 
F4.02 Time of stage 1 
Range: 0~6500s(min)【20.0s】
F4.03 Stage 2 setting 
Range: 000~323【000】 
F4.04 Time of stage 2 
Range: 0~6500s(min)【20.0s】
F4.05 Stage 3 setting 
Range: 000~323【000】 
F4.06 Time of stage 3 
Range: 0~6500s(min)【20.0s】
F4.07 Stage 4 setting 
Range: 000~323【000】 
F4.08 Time of stage 4 
Range: 0~6500s(min)【20.0s】
F4.09 Stage 5 setting 
Range: 000~323【000】 
F4.10 Time of stage 5 
Range: 0~6500s(min)【20.0s】
F4.11 Stage 6 setting 
Range: 000~323【000】 
F4.12 Time of stage 6 
Range: 0~6500s(min)【20.0s】
F4.13 Stage 7 setting 
Range: 000~323【000】 
F4.14 Time of stage 7 
Range: 0~6500s(min)【20.0s】
F4.01, F4.03, F4.05, F4.07, F4.09, F4.11 and F4.13 are 
used to configure the operating frequency, direction and 
Acc/Dec time of each PLC operating stage. These 
functions are all selected by digits, as shown in Fig. 5-28. 
The 7 stages of PLC can correspond to MS or close 
loop running.   
A       B
 
 C 
D
Frequency setting
0: Preset frequency i 
1: Determined by F0.00
2: Preset close-loop reference  i
3: Determined by F5.01
Acc/Dec time selection
0: Acc/Dec 1
1: Acc/Dec 2
2: Acc/Dec 3
3: Acc/Dec 4
Running direction selection
0: Forward
1: Reverse
2: Determined by operating 
command
Reserved
 
Fig. 5-28 Settings of PLC stage I(i=1~7) 
Where, 
A: thousand’s place B: Hundred’s place 
C: Ten’s place     D: Unit’s place 
Units’ place for setting stage i: 
0: Select preset frequency i, for example: F4.01 sets the 
parameter of stage 1, so the reference frequency is 
preset frequency 1 set by F3.23. Please refer to 
F3.23~F3.29 for definitions of preset frequencies. 
1: The frequency is determined by parameter F0.00 
2: Preset close-loop reference i, for example: F4.03 sets 
the parameter of stage 2, so the reference frequency is 
close-loop frequency 2 set by F5.21. Please refer to 
F5.20~F5.26 for definitions of preset close-loop 
reference. 
3: Determined by Parameter F5.01 
PLC can realize close-loop operation in a certain stage. 
Close-loop reference selectors can be preset close-loop 
reference i or determined by parameter F5.01; and the 
feedback is determined by F5.02. When the reference 
selector is determined by parameter F5.01, the terminals 
can be selected via preset close-loop reference. See 
F7.00~F7.07 and F5.20~F5.26 for details. 
 Note: 
When the PLC operating direction is determined by 
operating commands, the direction of the motor can be 
controlled by external terminals. For example: to run 
forward by closing FWD-COM terminal, and run reverse 
by closing REV-COM. If no command is given, the drive 
will run in the direction of last stage.