Chapter 5  Parameter Introductions      71 
EV2000 Series Universal Variable Speed Drive    User Manual 
②If panel control mode is used, press RUN to run the 
drive and press STOP to stop the drive. The preset 
frequency can be adjusted by pressing  ▲ and ▼. 
③If terminal control mode is used, connect FWD 
terminal to run forward and connect REV terminal to run 
reverse. The preset frequency is adjusted via VCI. 
④Terminal control mode is enabled after the drive is 
switched on. 
Remote
Multi-function input
Terminal  Xi
 
Local
Panel control
modeTerminal control
mode
 
Digital setting
mode 1
VCI input
PANEL/REMOTE
ENTER/DATA
Power on
 
Fig. 5-57 Remote and local control 
Set the parameters below to realize remote and local 
control: 
Set F0.03=1 to select terminal control mode and remote 
control is enabled after the drive is switched on; 
Set F7.00=28, F7.01=29, to select multi-function input 
terminal X1 and X2 to input operating commands; 
Set F7.08=1, to select 2-wire control mode 2. The drive 
run forward when FWD is enabled, and run reverse 
when REV is enabled; 
Set F9.07 to 020 to enable PANEL/REMOTE; 
If F9.00=041, then terminal control mode is bundled to 
VCI analog reference, and the panel control mode is 
bundled to digital reference setting 1. 
EV2000
U
V
W
PE
M
R
S
T
3-phase
AC 
supply
QF
PLC
COM
VRF
VCI
GND
.
.
.
.
.
REV
.
.
.
P24
FWD
4.7k
.
PE
K1
K2
.
X1
.
X2
K3
K4
 
Fig. 5-58 Wiring of remote and local control 
 Note: 
The parameter is default 000, that is, the frequency selector 
is not bundled with control mode. 
F9.01 Auxiliary reference 
frequency selector 
Range: 0~12【0】 
F9.02 Auxiliary analog 
reference frequency coefficient 
Range: 0.00~9.99
【1.00】 
F9.03 Initial auxiliary digital 
reference frequency 
Range: 0.00~650.0Hz
【0.00Hz】 
F9.04 Auxiliary digital 
reference frequency control 
Range: 000~111【000】
The preset frequency of EV2000 drive is the result out of 
the operation on the main reference frequency and 
auxiliary reference frequency. F9.01~F9.04 define the 
auxiliary reference frequency selector. Fig. 5-59 shows 
the process of operation.   
F1
Main ref. freq.
Common 
operating freq. 
(F0.00=0~5)
Preset freq. 
(F3.23~F3.29)
PLC operating freq. 
(F4.00~F4.14)
Close-loop 
operating freq.
(F5.00~F5.26)
Preset 
freq.
Coefficient 
adjustment
(F9.05, F9.06)
+
F2
F3 F4
Auxiliary 
ref. freq.
No auxiliary 
freq.(F9.01=0)
Digital setting of 
auxiliary 
freq.(F9.01=1~3)
Analog setting of 
auxiliary ref. 
freq.(F9.01=4~12)
 
Fig. 5-59 Preset frequency 
▲▼
Serial 
port
UPDN
CCI
PULSE
VCI
Analog
Digital
Aux. ref. freq.
Gain processing 
F9.02
Pre-processing
Initial value and sign 
of aux. ref.
F9.03 and F9.04
Setting F9.04
Setting of F1.00 
Setting 
of 
F9.01
 
Pre-processing
 
Fig. 5-60 Auxiliary reference frequency selector 
Auxiliary reference frequency is controlled by 
F9.01~F9.04. F9.01 defines the auxiliary reference 
frequency selector.