EasyManuals Logo

Emerson FloBoss 107 User Manual

Emerson FloBoss 107
152 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #106 background imageLoading...
Page #106 background image
FloBoss 107 Instruction Manual
6-2 Sensors and Transducers Revised June-2017
Note: You set values for MVS transmitters using ROCLINK
800’s MVS Sensor screen (Configure > I/O > MVS
Sensor).
Once you set a unique address for each transmitter, connect the
transmitters in a multi-drop (or “daisy-chair”) configuration (see
Figure 6-2). The only requirement for multi-drop wiring is that
you tie all like terminals together. This means all the “A”
terminals on the devices are electrically connected to the FB107’s
“A” terminal and so on.
MVS modules have removable terminal blocks for convenient
wiring and servicing. The terminal blocks can accommodate size
16 to 24 AWG.
The FB107 scans each MVS transmitter once every second,
accessing values for differential pressure, static pressure, and
temperature as inputs for flow calculations, history, calibration,
and alarming.
Each input unit is based on selected system units:
Differential
Pressure
Units
Static
Pressure
Units
Temperature
Units
English
Units
InH
2
O
PSI
Deg F
Metric
Units
kPa
kPa
Deg C
Figure 6-1. MVS Wiring

Table of Contents

Other manuals for Emerson FloBoss 107

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson FloBoss 107 and is the answer not in the manual?

Emerson FloBoss 107 Specifications

General IconGeneral
BrandEmerson
ModelFloBoss 107
CategoryController
LanguageEnglish

Related product manuals