FloBoss 107 Instruction Manual
7-12 Troubleshooting Revised June-2017
7.4.5 Troubleshooting Discrete Inputs
Jumper wire
PC running ROCLINK 800 software
Failure to exercise proper electrostatic discharge precautions, such
as wearing a grounded wrist strap may reset the processor or
damage electronic components, resulting in interrupted operations.
Ensure that the area is a safe operating environment.
1. Ensure that the I/O point is safe to remove from service.
2. Connect to ROCLINK 800.
3. Remove the wiring from the termination points.
4. Select Configure > I/O > DI Points.
5. Select the correct DI point number.
6. Place a jumper between the DI and the ground on the termination
block.
7. Using ROCLINK 800, verify that the status is on. (If the point is
configured for inverted operation, the status is off.)
8. Remove the jumper between the DI point and the ground on the
termination block.
9. View ROCLINK 800 and verify that the status is off. (If the point is
configured for inverted operation, the status is on.)
10. Reconnect the field wiring and place the point back into service.
7.4.6 Troubleshooting Discrete Outputs
Multimeter
PC running ROCLINK 800 software
Failure to exercise proper electrostatic discharge precautions, such
as wearing a grounded wrist strap may reset the processor or
damage electronic components, resulting in interrupted operations.
Ensure that the area is a safe operating environment.
1. Ensure that the I/O point is safe to remove from service.
2. Connect to ROCLINK 800.
3. Select Configure > I/O > DO Points.
4. Record the discrete output state shown on the Discrete Output screen.
5. Remove the wiring from the termination block.
6. Select the correct DO point number.