Chapter 5 iCOM Controller 57
WELLNESS BASIC1
Table 5-13 Descriptions of WELLNESS BASIC1 parameters
Parameters Default Setting range Description
S002 FREQ/YR 1pY 0pY ~ 12pY Maintenance frequency every year
S003 BONUS MM 0MM ~ 12MM Bonus setting
S004 PENALTY MM 0MM ~ 12MM Penalty setting
S005 LAST PM YY
S005 LAST PM MM
S005 LAST PM DD
-
Last maintenance. Year (YY), month (MM) and day (DD). This
parameter is read only
WELLNESS BASIC2
Table 5-14 Descriptions of WELLNESS BASIC2 parameters
Parameters Default Setting range Description
S006 NAME - - Service personnel setting
S007 CONFIRM No Yes, No Maintenance confirmation selection
S008 NEXT PM - - Calculated next maintenance. This parameter is read only
WELLNESS MOTOR
Table 5-15 Descriptions of WELLNESS MOTOR parameters
Parameters Default Description
S013 STARTS - Number of fan starts since the last maintenance
S014 RUN HRS hr Fan run hours since the last maintenance
S015 AVG RUN min Average fan run time calculated through number of fan starts and run hours
S016 BEST 1 Starts per day best
S017 WORST 24 Starts per day worst
S018 ALARMS 0 Number of alarms since the last maintenance
S019 BONUS 0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS COMP1
Table 5-16 Descriptions of WELLNESS COMP1 parameters
Parameters Default Description
S024 STARTS - Number of compressor 1 starts since the last maintenance
S025 RUN HRS hr Compressor 1 run hours since the last maintenance
S026 AVG RUN min Average compressor 1 run time calculated through the number of starts and run hours
S027 BEST 12 Starts per day best
S028 WORST 240 Starts per day worst
S029 HP AL 0 Number of high pressure alarms occurred to compressor 1 since the last maintenance
S030 LP AL 0 Number of low pressure alarms occurred to compressor 1 since the last maintenance
S031 OL AL 0 Number of overload alarms occurred to compressor 1 since the last maintenance
S032 DS HT AL 0
Number of digital scroll high temperature alarms occurred to compressor 1 since the last
maintenance
S033 BONUS 0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS COMP2
Table 5-17 Descriptions of WELLNESS COMP2 parameters
Parameters Default Description
S035 STARTS - Number of compressor 2 starts since the last maintenance
S036 RUN HRS hr Compressor 2 run hours since the last maintenance
S037 AVG RUN min Average compressor 2 run time calculated through the number of starts and run hours
S038 BEST 12 Starts per day best
S039 WORST 240 Starts per day worst
S040 HP AL 0 Number of high pressure alarms occurred to compressor 2 since the last maintenance
S041 LP AL 0 Number of low pressure alarms occurred to compressor 2 since the last maintenance
Liebert.PEX2 Series Air Conditioner User Manual