58 Chapter 5 iCOM Controller
Liebert.PEX2 Series Air Conditioner User Manual
Parameters Default Description
S042 OL AL 0 Number of overload alarms occurred to compressor 2 since the last maintenance
S043 DS HT AL 0
Number of digital scroll high temperature alarms occurred to compressor 2 since the last
maintenance
S044 BONUS 0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS HEAT1
Table 5-18 Descriptions of WELLNESS HEAT1 parameters
Parameters Default Description
S046 STARTS - Number of electric heater 1 starts since the last maintenance
S047 RUN HRS hr Electric heater 1 run hours since the last maintenance
S048 AVG RUN min Average electric heater 1 run time calculated through the number of starts and run hours
S049 BEST 24 Starts per day best
S050 WORST 240 Starts per day worst
S051 ALARMS 0 Number of high pressure alarms since the last maintenance
S052 BONUS 0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS HEAT2
Table 5-19 Descriptions of WELLNESS HEAT2 parameters
Parameters Default Description
S057 STARTS - Number of electric heater 2 starts since the last maintenance
S058 RUN HRS hr Electric heater 2 run hours since the last maintenance
S059 AVG RUN min Average electric heater 2 run time calculated through the number of starts and run hours
S060 BEST 24 Starts per day best
S061 WORST 240 Starts per day worst
S062 ALARMS 0 Number of high pressure alarms since the last maintenance
S063 BONUS 0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS HEAT3
Table 5-20 Descriptions of WELLNESS HEAT3 parameters
Parameters Default Description
S068 STARTS - Number of electric heater 3 starts since the last maintenance
S069 RUN HRS hr Electric heater 3 run hours since the last maintenance
S070 AVG RUN min Average electric heater 3 run time calculated through the number of starts and run hours
S071 BEST 24 Starts per day best
S072 WORST 240 Starts per day worst
S073 ALARMS 0 Number of high pressure alarms since the last maintenance
S074 BONUS 0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance
WELLNESS HUM
Table 5-21 Descriptions of WELLNESS HUM parameters
Parameters Default Description
S079 STARTS - Number of humidifier starts since the last maintenance
S080 RUN HRS hr Humidifier run hours since the last maintenance
S081 AVG RUN min Average humidifier run time calculated through the number of starts and run hours
S082 BEST 24 Starts per day best
S083 WORST 240 Starts per day worst
S084 ALARMS 0 Number of high pressure alarms since the last maintenance
S085 BONUS 0MM
Bonus amount. Actual bonus calculated through the number of starts and average run time.
This value determines the time for the next maintenance