SAG582127000 System Application Guide
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Page 110 of 125
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Fuse/
Circuit
Breaker
Amperage
Recm 90
°
C Wire Size
(1)
4 AWG 2 AWG 1/0 AWG 2/0 AWG 3/0 AWG 4/0 AWG
250
kcmil
350
kcmil
Loop Length (feet)
(2)
90A 41
(3)
66
(3, 4)
105
(3, 4)
133
(4)
-- -- -- --
100A
--
59
(3, 4)
95
(3, 4)
119
(3, 4)
-- -- -- --
125A
--
47
(3)
76
(3, 4)
95
(3, 4)
120
(4)
-- -- --
150A
-- --
63
(3, 4)
79
(3, 4)
100
(3, 4)
-- -- --
200A
-- -- -- --
75
(3, 4)
95
(3, 4)
112
(3, 4)
--
250A
-- -- -- -- --
76
(3, 4,
7)
90
(3, 4,
7)
126
(3, 4,
7)
Recommended Crimp Lug
Lug
(5)
245346800 245346900
245393500
(6)
245393600
(6)
245393700
(6)
245393800
(6)
514872
(6)
514873
(6)
Lug
(8, 9)
-- 245348200 245347100 245347200 245347300 245347400 245347500 245347700
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310.15 (B) (16) for
copper wire at 90°C conductor temperature. For operation in countries where the NEC is not recognized,
follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for
the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 1/4" bolt clearance hole, 5/8" centers. Refer to drawing 031110100 for lug crimping
information.
6
Special application crimp lug / strap combination.
7
MUST USE P/N 514717 Lug Adapter Busbar for lugs having 1/4" bolt clearance hole, 5/8" centers.
8
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping
information.
9
MUST USE P/N 522786 or 534449 Lug Adapter Busbar for 125A-200A circuit breakers or P/N 514714
Lug Adapter Busbar Kit for 250A circuit breakers.