SAG582127000 System Application Guide
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Page 12 of 125
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
a) Order the front access DC Input Termination Assembly per List 45, 46, or 47 if module
mounting shelf 58870500040 ordered (or order module mounting shelves with terminal
blocks, 58870500041, 58870500042).
b) Order converter modules as required, P/N 1C400483500E.
c) Order a module mounting position blank cover panel, P/N 21140440, for each empty module
mounting position in the system, as desired.
5) 588705300 Rectifier/Converter Option: Order interface components for module mounting shelf(s) Spec.
No. 588705300 as required per List 32. Order field expansion module mounting shelf(s) per List 33.
Order module mounting shelf(s) per PD588705300.
a) Order the front access AC Input Termination Assembly per List 40, 41, or 42 (or order module
mounting shelves with AC input cable assemblies, see PD588705300).
b) Order rectifier modules as required, P/N 1R482000E3.
c) Order optional converter interface components per List 60.
d) Order optional DC-DC converter modules as required, P/N 1C48241500.
6) Order battery trays as required per List 93.
a) Order batteries as required per Batteriesunder ACCESSORY DESCRIPTIONS.
b) Order Optional Battery Tray Battery Disconnect Circuit Breaker and Housing Kits” as required.
c) Order Optional Battery Tray Front Battery Cover Kitsas required.
List 2: 1
st
Supplemental Bay Common Equipment (Power and Distribution or Distribution Only),
Located In-Line with Main Bay
Features
Provides common equipment for one bussed “power and distribution or distribution only” bay rated for up
to 2000 amperes of distribution. Includes interbay power busbars and communications cable.
Mounts to either left or right side of List 1 Main Bay.
Accepts one (1) distribution cabinet (options are 3-row or 4-row cabinet).
Includes SM-DU (provides bay interface to ACU+ Controller).
Accepts up to six (6) module mounting shelves Spec. No. 588705000 (including expansion shelves).
or
Accepts up to six (6) module mounting shelves Spec. No. 588705300 (including expansion shelves).
Restrictions
When the system is equipped with a List 40, 41, 42, 45, 46, or 47 front access Input Termination Assembly,
refer to the restrictions under these list descriptions.
Will not accept List 21 and 22 distribution cabinet.
(List 21 and 22 are not provided with connection points for interbay busbars.)
Will not accept List 60 converter interface components.
Will not accept dual voltage distribution panels.
Order maximum of one (1) List 2 or List 5 per Power System.
Cannot be used when List 5 is ordered. Order List 2 or List 5, not both.
Rear access required for installation of inter-bay busbars.
If low voltage disconnect (List LL or List LB) is to be included, the Main Bay (List 1) of the system must also
have low voltage disconnect (List LL or List LB).
Ordering Notes
1) Order a relay rack or shipping brackets per “Relay Racks and Shipping Brackets” under ACCESSORY
DESCRIPTIONS. If required, order relay rack transition plates per “Transition Plates to Mount Relay
Rack on Top of GNB Absolyte IIP Batteriesunder ACCESSORY DESCRIPTIONS.
2) Order one (1) List 23 or 24 distribution cabinet.