SAG582127000 System Application Guide
Issue AF, February 26, 2014 Spec. No. 582127000 (Model 721
NPBB)
Page 72 of 125
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
GMT Type Load Distribution Fuses
Features
An optional “Bullet Nose Type 6-Position GMT Distribution Fuse Block, P/N 550224” is available for
additional load distribution.
Restrictions
When used for power distribution, load should not exceed 80% of device rating, except 10 and 15 amp fuses,
for which load should not exceed 70% of device rating.
Ordering Notes
1) Order fuses as required per Table 13.
Ampere Rating Part Number Fuse Color
18/100 (GMT-A)
248610301
---
1/4
248610200
VIOLET
1/2
248610300
RED
3/4
248610500
BROWN
1-1/3
248610700
WHITE
2
248610800
ORANGE
3
248610900
BLUE
5
248611000
GREEN
7-1/2
248611300
BLACK-WHITE
10
248611200
RED-WHITE
15
248611500
RED-BLUE
Replacement
Safety Fuse
Cover (GMT-Y)
102774 ---
Replacement
Dummy Fuse
248872600 ---
Table 13
GMT Fuses