System Application Guide SAG582127000
Spec. No. 582127000 (Model 721
NPBB) Issue AF, February 26, 2014
Page 73 of 125
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
GJ/218 Type Circuit Breakers
Restrictions
For use in Lists AC, AD, BC, and BD.
Load should not exceed 80% of device rating.
Refer to Table 14 for required distribution row
mounting positions.
Ordering Notes
1) Order circuit breakers as required per
Table 14.
2) Order a jumper kit as required for each
circuit breaker per Table 14.
3) See Table 28 for recommended load
distribution wire sizes and lugs.
Ampere
Rating
No. of
Positions
P/N
Electrical/
Mechanical Trip
1
without
Internal
Shunt
P/N
Electrical Trip
2
without
Internal
Shunt
Breaker
Mounting
Kit
(without
Shunt)
P/N
Electrical/
Mechanical Trip
1
with
Internal Shunt
(25mV @ full
3
P/N
Electrical Trip
2
with
Internal Shunt
(25mV @ full
rated load)
3
Breaker
Mounting
Kit (with
Shunt)
See Table 28 for recommended load distribution wire sizes and lugs.
1, 2
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical or manual trip condition.
2
Provides an alarm during an electrical trip condition only.
3
Extended shunt leads are 22 AWG stranded wire, approximately 7-10 ft. long from exit point at bottom of
distribution cabinet. Each shunt lead is equipped with a 49.9 ohm current limiting resistor. Shunt leads are
factory wired to SM-DU+ (if ordered).
Note: Electrical Trip only circuit breakers are not typically used for battery disconnect circuit breakers.
Table 14
GJ/218 Circuit Breakers