Special Application Crimp Lug / Strap Combination Table
Features
♦ Straps two fuseholder/circuit breaker wiring positions together, and provides a crimp-type lug which
allows distribution wiring up to 350 kcmil size (maximum size of wire to be connected to a single position
is 2 AWG). Designed for use with 125A and larger bullet nose-type circuit breakers or TPS/TLS-type
fuses, which require at least two mounting positions.
Restrictions
If used with bullet nose-type circuit breakers or TPS/TLS-type fuses smaller than 125A, an empty mounting
position is required adjacent to the distribution device.
Ordering Notes
1) Specify part number from Table 9 for desired lead size.
Lead Size Part Number
Table 9
Special Application Crimp Lug / Strap Combination
(Two-Hole Lug, 1/4” Bolt Clearance Hole, 5/8” Centers)