42
Safety Manual
00809-0200-5100, Rev GB
Installation and Configuration
February 2017
Installation and Configuration
11. Click the Print Screen button to print a copy of the current Safety Alarm window. The
printed copy can be used at a future occasion to check that no changes have been done
to the SIL Rosemount Tank Gauging Safety System since last time it was configured.
12. It is recommended to make a backup of the 5900 configuration when the safety setup
is finished. A copy of the 5900 Holding Registers can be stored to disk by using the
“Save Database to File” option
(1)
. You may also make a backup copy of the Input
Registers which may be useful for future troubleshooting.
(1) See the Rosemount Tank Gauging System Configuration Manual (Document No. 00809-0300-5100) or the Rosemount 5900S
Reference Manual (Document No. 00809-0100-5900).