56
Safety Manual
00809-0200-5100, Rev GB
Proof Test
February 2017
Proof Test
4. Verify that the SIL Reference Reflector/LPG Pin Distance and SIL Reference Reflector/LPG Pin
Amplitude parameters are displayed. In case no Reference Reflector is installed, these
parameters will be equal to zero and the Test SIL High Alarm button will be disabled.
5. Click the Test SIL High Alarm button.
6. Click the Accept button to continue.