Safety Manual
00809-0200-5100, Rev GB
Disabling the SIL High Alarm
February 2017
Disabling the SIL High Alarm
To disable the SIL High Alarm Limit function:
1. Ensure that the safety system is unlocked, i.e. in the Not Approved state (see
“Changing the current alarm configuration” on page 45 for information).
2. In the Safety Alarm window, click the Change Parameters button to open the Change
Safety Alarm Parameters window.
The following options are available for disabling the SIL High Alarm Limit:
Table E-1. Options for disabling SIL High Alarm Limit
3. In the “SIL High Alarm Limit” drop-down list, choose the desired option (see Tabl e E-1 )
and click the Apply button to store the configuration.
4. Change Safety Mode to “Approved”. See “Safety alarm configuration procedure” on
page 32 for more information.
Option Description
0 Disables SIL High Alarm Limit.
1 Disables SIL High Alarm Limit and no SIL High Alarm will be triggered if
the 5900 gauge loses track of the product surface.
SIL High Alarm Limit