Definitions of analog input function block system parameters (continued)Table 7-20:
Parameter Index number Units Description
HI_ALM 34 None The HI alarm data, which in-
cludes a value of the alarm,
a timestamp of occurrence,
and the state of the alarm.
HI_HI_ALM 33 None The HI HI alarm data, which
includes a value of the
alarm, a timestamp of oc-
currence, and the state of
the alarm.
HI_HI_LIM 26 EU of PV_SCALE The setting for the alarm
limit used to detect the HI
HI alarm condition.
HI_HI_PRI 25 None The priority of the HI HI
alarm.
HI_LIM 28 EU of PV_SCALE The setting for the alarm
limit used to detect the HI
alarm condition.
HI_PRI 27 None The priority of the HI alarm.
IO_OPTS 13 None Allows the selection of in-
put/output options used to
alter the PV. Low cutoff ena-
bled is the only selectable
option.
L_TYPE 16 None Linearization type. Deter-
mines whether the field val-
ue is used directly (Direct),
is converted linearly (Indi-
rect), or is converted with
the square root (Indirect
Square Root).
LO_ALM 35 None The LO alarm data, which in-
cludes a value of the alarm,
a timestamp of occurrence,
and the state of the alarm.
LO_LIM 30 EU of PV_SCALE The setting for the alarm
limit used to detect the LO
alarm condition.
LO_LO_ALM 36 None The LO LO alarm data, which
includes a value of the
alarm, a timestamp of oc-
currence, and the state of
the alarm.
Foundation Fieldbus
Reference Manual 133