EasyManua.ls Logo

Emerson Rosemount OCX 8800 - Proportional;integral;derivative (PID) function block

Emerson Rosemount OCX 8800
300 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.9 Proportional/integral/derivative (PID) function
block
The PID function block combines all of the necessary logic to perform proportional/
integral/derivative (PID) control. The block supports mode control, signal scaling and
limiting, feedforward control, override tracking, alarm limit detection, and signal status
propagation.
Proportional/integral/derivative (PID) function blockFigure 7-12:
BKCAL_IN = The analog input value and status from another block's BKCAL_OUT output that is
used for backward output tracking for bumpless transfer and to pass limit status.
CAS_IN = The remote setpoint value from another function block.
FF_VAL = The feedfoward control input value and status.
IN = The connection for the process variable from another function block.
TRK_IN_D = Initiates the external tracking function.
TRK_VAL = The value after scaling applied to OUT in Local Override mode.
BKCAL_OUT = The value and status required by the BKCAL_IN input of another function block to
prevent reset windup and to provide bumpless transfer to closed loop control.
OUT = The block output and status.
The block supports two forms of the PID equation: Standard and Series. You can choose
the appropriate equation using the FORM parameter. The standard ISA PID equation is the
default selection.
Foundation Fieldbus
Reference Manual 149

Table of Contents

Related product manuals