Troubleshooting (continued)Table 7-29:
Symptom Possible causes Corrective action
Mode sheds form ROUT to MAN 1. Remote output value 1. Host system is not writing ROUT_IN
with a quality and status of good
cascade within shed time (see 2 be-
low).
2. Shed timer 2. The mode shed timer, SHED_RCAS,
in the resource block is shed too low.
Increase the value.
Process and/or block alarms will not
work.
1. Features 1. FEATURES_SEL does not have Alerts
enabled. Enable the Alerts bit.
2. Notification 2. LIM_NOTIFY is not high enough. Set
equal to MAX_NOTIFY.
3. Status options 3. STATUS_OPS has Propagate Fault For-
ward bit set. This should be cleared to
cause an alarm to occur.