S4K2UC SERIES USER MANUAL | 15
2.0 Installation
2.1 Unpacking & Inspection
Unpack the UPS and conduct the following checks:
• Inspect the UPS for shipping damage. If any shipping damage is found, report it to the carrier and your local dealer
or SolaHD representative immediately.
• Check the accessories against the delivery list. If there are any discrepancies, contact your local dealer or SolaHD
representative immediately.
2.2 What’s Included
• Compact disk containing: MultiLink, conguration program and user manual
• One, 6-1/2 ft. (2 m) long USB cable
• Mounting hardware, including screws and handles
• Two plastic tower stand sets (four pieces total)
• Terminal block communication terminals
• Warnings, Safety Instructions booklet and WEEE recycling sheet (ISO 14001 compliance)
NOTE: The S4K2UC external battery cabinet shipping package includes one battery cabinet, two spacers for tower
conguration and one DC power cable.
2.3 Preparation for Installation
2.3.1 Installation Environment
• Install the UPS indoors in a controlled environment, where it cannot be accidentally turned o. The installation envi-
ronment should meet the specications listed in “9.0 Specications”.
• Place the UPS in an area of unrestricted airow around the unit, away from water, ammable liquids, gases, corro-
sives, and conductive contaminants. Avoid direct sunlight.
NOTE: Operating the UPS in temperatures above 25°C (77°F) reduces battery life.
2.3.2 Installation Clearances
Maintain at least 4 inches (100 mm) clearance in the front and rear of the UPS. Do not obstruct the air inlets on the front
panel and rear panel of the UPS; blocking the air inlets reduces ventilation and heat dissipation, shortening the service
life of the unit.