42 | 9.0 Specications
9.0 Specications
Table 11: UPS Specications
Parameters
Model
S4K2U700C S4K2U1000C S4K2U1500C S4K2U2000C S4K2U3000C
DIMENSIONS, D x W x H, in. [mm]
Unit 19.7 x 16.9 x 3.4 [497 x 430 x 85]
23.7 x 16.9 x 3.4
[602 x 430 x 85]
Shipping 25.5 x 23.9 x 10.6 [647 x 607 x 270]
29.4 x 23.4 x 10.6
[747 x 607 x 270]
WEIGHT, lb. [kg]
Unit 37.0 [16.8] 51.1 [23.2] 51.1 [23.2] 71.4 [32.4]
Shipping 44.1 [20.0] 57.3 [26.0] 57.3 [26.0] 79.4 [36.0]
INPUT AC PARAMETERS
Voltage range (typical) 120 V ac nominal; variable based on output load
90% to 100% Loading 90 VAC/140 VAC 102 VAC/140 VAC
70% to 90% Loading 86 VAC/140 VAC 96 VAC/140 VAC
30% to 70% Loading 77 VAC/140 VAC 84 VAC/140 VAC
0% to 30% Loading 60 VAC/140 VAC 60 VAC/140 VAC
Power factor 0.99
Frequency 40 Hz to 70 Hz; auto sensing
Input power cord 10 ft. attached with NEMA 5-15P plug
10 ft. attached with
NEMA 5-20P plug
10 ft. attached with
NEMA L5-30P plug
OUTPUT AC PARAMETERS
Output receptacles 5-15R x 6 5-20R x 6 L5-30R x 1 + 5-20R x 6
Voltage 110/115/120 VAC (user-congurable) ±3%
Waveform Sine wave
Utility (VAC) Mode overload 200% for 2 seconds; 150% for 50 seconds with transfer to bypass
Power factor 0.90
BATTERY
Type Valve-regulated, non-spillable, lead acid
Qty x V x Rating 4 x 12 V x 5.0 Ah 4 x 12 V x 7.2 Ah 4 x 12 V x 9.0 Ah 6 x 12 V x 9.0 Ah
Battery mfr./Part number Panasonic/UP-RW1236; CSB/GP 1272 Panasonic/UP-RW1245; CSB/HR 1234W F2
Backup time See Table 14
Recharge time 3 hours to 90% capacity after full discharge with 100% load until UPS auto shutdown (internal batteries only)
ENVIRONMENTAL REQUIREMENTS
Operating temperature 0°C to +40°C [+32°F to +104°F]; see Table 13 for operating temperature parameters
Storage temperatures -15°C to +50°C [+5°F to +122°F]
Relative humidity 0% to 95%, non-condensing
Operating elevation Up to 10,000 ft. [3,000 m]