8. INSTALLER SCREENS
8.2.1 - Room temp. differential
The Room temp differential applies to the Room Temperature
Set for the Thermostat call (
or ).
The consent shall be activated when:
• in heating → Room temperature
< Room temp. Set – Room temp.
differential
• in cooling → Room temperature
> Room temp. Set – Room temp.
differential
Consent is disabled when:
• in heating → Room temperature
> Room temp Set
• in cooling → Room temperature
< Room temp Set
Set temp
environment
Differential
temp. environment
Consent
Thermostat consent in heating
time
Consent
time
Cooling thermostat consent
temp.
environment
Consent
time
Consent
temp.
environment
time
Humidistat consent
Consent
Consent
temp. of dew
Humidistat consent
temp. of dew
Consens
Set temp
or ambient
humidity
Differential
Set temp
environment
Temp
environment
Differential
temp. environment
Temp
environment
Humidistat consent
relative humidity /
temp. of dew
Cooling thermostat consent
Thermostat consent in heating
Set temp
environment
Differential
temp. environment
Consent
Thermostat consent in heating
time
Consent
time
Cooling thermostat consent
temp.
Consent
time
Consent
temp.
time
Humidistat consent
Consent
Consent
temp. of dew
Humidistat consent
temp. of dew
Consens
Set temp
or ambient
humidity
Differential
Set temp
environment
Differential
temp. environment
Temp
environment
Humidistat consent
relative humidity /
temp. of dew
Cooling thermostat consent
Thermostat consent in heating
time
time
8.2.2 Booster Differential
The Booster Differential applies to the Room Temperature Set
for calling the automatic Boost (
).
The logic of activating/deactivating the automatic Boost is com-
pletely similar to that of the consent of the Thermostat,
replacing the Room temp differential with the Booster differen-
tial.
8.2.3 Room humidity differential
The Room humidity differential applies to the room humidity
Set pointfor the Humidistat call (
).
NOTE:
The following values canbe used as a referencefor the room
humidity Set point:
- relative humidity →setting a value between 30 % and 99 %
- dew temperature → setting a value between 10.0°C and 29.9°C
The Room humidity differential assumes the same value as the
room humidity Set point.
Consent is activated, depending on the reference used, when:
• Relative humidity > Room humidity Set point (RH %) + Room
humidity differential (RH %)
• Dew temperature > Dew temp Set point (°C) + Dew temp
differential (°C)
Consent is disabled, depending on the reference used, when:
• Relative humidity < Room humidity set point (RH %)
• Dew temperature < Room humidity set point (°C)
Set temp
environment
Differential
temp. environment
Consent
Thermostat consent in heating
time
Consent
time
Cooling thermostat consent
temp.
environment
Consent
time
Consent
temp.
environment
time
Humidistat consent
Consent
Consent
temp. of dew
Humidistat consent
temp. of dew
Consens
Set temp
or ambient
humidity
Differential
Set temp
environment
Temp
environment
Differential
temp. environment
Temp
environment
Humidistat consent
temp. of dew
Cooling thermostat consent
Thermostat consent in heating
time
time
Set temp
environment
Differential
temp. environment
Consent
Thermostat consent in heating
time
Consent
time
Cooling thermostat consent
temp.
environment
Consent
time
Consent
temp.
environment
time
Humidistat consent
Consent
Consent
temp. of dew
Humidistat consent
Consens
Set temp
or ambient
humidity
Differential
Set temp
environment
Temp
environment
Differential
temp. environment
Temp
environment
Humidistat consent
relative humidity /
temp. of dew
Cooling thermostat consent
Thermostat consent in heating
time
time