6.2 Unit fixing to the anchor bolts
- Ensure that dimensions of the opening on the false ceiling are adequa-
tely sized to the unit installation
- Dispose all piping (refrigerant and condensation drain) and electrical
wires (connection between indoor and external unit) of the indoor unit.
- Install the anchor bolts when rooms already dispose of ceiling.
Otherwise if ceiling is new you will use indoor plugs
- Insert the mounting brackets of the indoor unit on the anchor bolts for
hanging the unit. Make sure to insert a washer and a nut at both ends
of each bracket.
6.1 Installation template fixing and positioning
of the hole on the wall
(1) Determine the installation location of the unit by paying attention
to the space for pipes, wiring and maintenance.
(2) Cut an appropriately sized opening in the false ceiling
using as a reference the cardboard template supplied with the unit.
Over1500mm
Over1500mm
Over 1500mm
Over 1500mm
L1 L1
L
575 > 590 mm
570 mm
400 mm
0 mm16
Drilling and fixing of anchor bolts
For concrete
For steel floor
150 a 160 mm
Screw
(100 a 150kg)
Steel bars
Bolts
of suspension
(w3/8 - M10)
Slab a
shape of
Bolts
of suspension
(w3/8 - M10)
For wooden floor
Wood auction (60mm a 90mm)
Wood auction
Nut
Round washer
Square washer
Nut
Suspension bolt
Suspension bolt (supplied)
Nut (included)
* Washer with insulation (accessory)
Suspension bracket (included in the internal unit)
* Washer (accessory)
Nut (included)
Surface of the ceiling
181
About 52
About 52
6. INSTALLATION OF THE INDOOR UNIT
Installation and maintenance activities on the air conditioners can
be done by personnel and companies holding appropriate certified
according to the Regulation (EC) nr. 2015/2067 which provides the
minimum requirements of the companies and of the personnel
about fixed units of refrigeration, air condition and heating pumps
which contain some fluorinated greenhouse gases, according to
the Regulation (EC) nr. 517/2014 of the European Parliament and of
the Council.
- Installation must be performed by qualified and authorized personnel.
- Do not attempt to install the unit by yourself.
- For any repairs, contact the service centre.
- Repairs of an electrical nature must be performed by qualified
electricians.
- Improper operations may cause serious harm to the user.
- You can find a list of service centres at the website
www.emmeti.com
The correct installation of the air conditioner guarantees its efficient
operation.
The air conditioner assure its efficiency.
Therefore we invite you to follow the instructions carefully about posi-
tioning, installation, connection and test listed in these manuals.
The unit must be installed in compliance with the regulations
local and national in therm of security.
Connect the unit to the power supply only after completing
the installation.
For the installation of the unit a horizontal position must be guaranteed
of the same.
Choose a suitable location for installing the unit
make condensate drain and connection to the outdoor unit simple.
Make sure there is enough space for installation and maintenance
of the unit.
Make sure that the distance between the floor and the indoor unit is
greater
at 1800mm.
Ensure that the installation site can withstand a load of at least 4 times
the weight of the unit
CAUTION
Danger cut: use of gloves.
If the conditions are met Arrange for work at height.