Assigning RCCs
The newly added RCCs should now be assigned.
From Unassigned Dev Assign Device Assign RCCs Dev 000 of 001
changing to Done 001 of 001 (once complete).
To Exit
BACK
Device Installation & Programming
Wireless devices can be programmed to their relevant RCC prior to their installation. The devices must
be powered up and then added to their relevant RCCs, by pressing their log on buttons. For more
information about these devices see the Device Power, Logon & Ident Orientations section.
From Front Display Add New Device Select Desired RCC 01 Set Loop 1 Addr 003
Add By Log On Press Dev Log On ‘press the devices log on button, followed by Add Dev 03456 Y?
New Addr L1 A003.
To Exit
The device has now been added to the Radio Hub and should be installed in its location, prior to the
next step of assigning the device to its relevant RCC. See the relevant devices installation instructions,
for more information.
Assigning Devices
The newly added devices must now be assigned. This can be achieved by selecting;
From Unassigned Dev Assign Device Assign All Dev 000 of 003 changing to
Done 003 of 003 (once complete)
To Exit
BACK
BACK
Page 9 of 40©2019 EMS Ltd. All rights reserved. MK98 Iss17 05/04/2019 AJM

Other manuals for EMS FIRECELL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the EMS FIRECELL and is the answer not in the manual?

EMS FIRECELL Specifications

General IconGeneral
Frequency868 MHz
Operating Temperature-10°C to +55°C
CommunicationWireless
ComplianceEN54-25
Devices SupportedSounders
Power SupplyLithium battery
Humidity RangeUp to 95% RH, non-condensing
CompatibilityEMS Firecell System
TypeWireless Fire Alarm