EMS 5000 FIREPOINT
©2015 EMS Security Group Ltd. All rights reserved. TSD258 Iss 3 25/06/15 AJM
21
10 Press Yes key and the screen will now
display:
11 Press key once and the screen will now
display: (Make note of the status the zones is
in e.g. ALL, the status will need to be changed
back Later)
12 Press Yes key twice and the screen will now
display: (notice as the Y key is press the status
changes)
13 Press key once and the screen will now
display:
14 Press Yes key and the screen will now
display:
15 Press key once and the screen will now
display:
16 Press Yes key twice and the screen will now
display: (notice as the Y key is press the status
changes)
This needs to be repeated until all the zones are in test, then continue
to step 17
17 Press No key three times and the screen will
now display:
18 Turn the Control key switch to the off position
and the screen will now display:
The devices are now ready to be activated, this includes smoking
detectors and triggering call points. When a device is activated the
5000 FirePoint will go into fire, the display will show TEST ALARM and
display the device number and text description. The Sounders/Relays
will not activate.
NOTE: When smoking detectors the LED stays on for 20 minutes.
NOTE: FOR MULTI PANEL INSTALLATIONS ALL ZONES ON ALL PANELS
MUST BE PUT INTO TEST BEFORE TESTING IS STARTED.
| ** Zone Status ** |
>Zone is: 01 <
|Status : ALL |
Yes= Select Time
Panel in Access
Date Time
|Zone is : 01 |
>Status : ALL <
|^^^^^^^^^^^^^^^^|
Yes= Select Time
|Zone is : 01 |
>Status : Test <
|^^^^^^^^^^^^^^^^|
Yes= Select Time
| ** Zone Status ** |
>Zone is: 01 <
|Status : Test |
Yes= Select Time
| ** Zone Status ** |
>Zone is: 02 <
|Status : ALL |
Yes= Select Time
|Zone is : 02 |
>Status : ALL <
|^^^^^^^^^^^^^^^^|
Yes= Select Time
|Zone is : 02 |
>Status : Test <
|^^^^^^^^^^^^^^^^|
Yes= Select Time