©2015 EMS Security Group Ltd. All rights reserved. TSD258 Iss 3 25/06/15 AJM
27
15 Press key one times and the screen will
display:
16 Press Yes key, the screen will stay the same but
the test LED will start flashing to show that all
the zones are in test.
NOTE: Check the other panels to make sure the test LED has stopped
flashing to ensure Sounders/Relays are ready to activate.
15. How To Test Individual Sounders
To test individual sounders on the 5000 FirePoint, insert the key into the panel
controls keyswitch, located at the right of the panel.
Step Action Screen Display
No
1 Turn the key to the on position and the
screen will display:
2 Press 0 key and the screen will now display:
3 Press key three times and the screen will
display:
4 Press Yes key and the screen will now display:
5 Press key four times and the screen will
display:
6 Press Yes key and the screen will now display:
| SINGLE |
>ALL <
| TWO PHASE |
Yes= Select Time
| SINGLE |
>ALL <
| TWO PHASE |
Yes= Select Time
|***Options ****|
>Passwords <
|Time and Date |
Yes =Select Time
|Logging |
>Fire System Opts<
|Remote Access |
Yes = select Time
|** Fire system **|
>Dev. Isolate/Test<
| Net. Isolate/Test |
Yes= Select Time
|Brigade Isolate |
>Engineers Config<
|Printer Options |
Yes= Select Time
Enter Your PIN
For Access>
Then Press YES
Time
Panel in Access
Date Time