EMS 5000 FIREPOINT
©2015 EMS Security Group Ltd. All rights reserved. TSD258 Iss 3 25/06/15 AJM
28
7 Press 221100 then press Yes key and the
screen will display:
8 Press key once and the screen will display:
9 Press Yes key twice and the screen will now
display: (the first press of Y enters you into
the sounder options menu the second press
of Y does a configure stop)
10 Press key twice and the screen will display:
11 Press Yes key and the screen will now
display:
12 Press the Yes key to toggle though the
device numbers until you get to the sounder
that requires testing. (e.g. 025)
13 Press key once and the screen will display:
14 Press Yes key to toggle though the different
types of action commands. (E.g. press Y key
seven times takes you to test)
There are 11 different types are actions :-
a) FIRE: The selected sounder will activate with the fire tone.
b) EVAC: The selected sounder will activate with the evacuate tone.
c) BOMB: The selected sounder will activate with the bomb tone.
d) LESS GHNG: The selected sounder will do a set of lesson change
beeps.
e) AUX ON : Not Used
|** Eng.; Config ** |
>Device Database <
|Sounder Options |
Yes= Select Time
|Sounder Config |
>Configure STOP <
| Configure START |
Yes= Select Time
| Configure START |
>Configure ONE <
^^^^^^^^^^^^^^^^^
Yes= Select Time
|** Configure ** |
>Sounder : ALL CFGD<
|Action : FIRE |
Yes= Select Time
|** Configure ** |
>Sounder : 025 <
|Action : FIRE |
Yes= Select Time
|Sounder : 025 |
>Action : FIRE <
|Do Action |
Yes= Select Time
|Sounder : 025 |
>Action : TEST <
|Do Action |
Yes= Select Time
|Device Database |
>Sounder Options <
|List Options |
Yes= Select Time