Semi-automatic
entry
Requirements for semi-automatic entry of
the linearisation curve are as follows:
The vessel can be filled for e.g. empty/full
calibration and for linearisation can be
emptied as described below. The level is
automatically determined from the
hydrostatic pressure. The appropriate
volumeisgivenin%.
The measured value is supplied as a
volume.
Note!
For step 1, you can also carry out a
zero correction according to the
procedure described in Chapter 5.1,
page 27.
A dry calibration can also be made
using steps 1-3, see page 34.
In edit mode V3H6 = Manual, you can
delete individual points in a linearisation
table entering "9999" for level or
volume. But first activate the
linearisation table.
Entering the pairs of values for the
linearisation curve is done after a
calibration with reference pressure or a dry
calibration in %. The procedure with
reference pressure is then carried out as
described below.
# Matrix Path through the
menus
Entry
Fill the vessel to the zero point
1 Set the display to "0" by adopting an acting
bias pressure.
V0H6 Sets bias
pressure
automatically Confirm
2 Adopt the acting pressure for the lower
range-value (empty)
V0H3 Sets 4 mA
automatically Confirm
Fill the vessel to the end point (full)
3 Adopt the acting pressure for the upper
range-value
V0H4 Sets 20 mA
automatically Confirm
# Changing product?
see "Density Correction" page 33
Main group: Linearisation
4 Select linearisation mode "semi-automatic
entry"
V3H6 Operation mode
semi-automatic Confirm
5 Enter the table
V3H7 Line No. 7
Confirm
V3H8 Input level
Confirm
The actual level is automatically determined
V3H9 Set volume e.g. 100%
Confirm
Repeat step 5 until all points have been
entered.
6 Activate the table
V3H6 Activate
table Confirm
7 Select the operation mode "Level manual"
V3H0 Level
manual Confirm
8 Enter the level or volume at the minimum level
V3H1 Display at
4 mA
e.g. 0 (hl)
Confirm
9 Enter the level or volume at the maximum level
V3H2 Display at
20 mA
e.g. 10 (hl)
Confirm
10 Select the level or volume units
(Select unit from the tables on page 32)
V3H3 Unit after
linearisation
e.g. hl
Confirm
1
4
6
5
3
2
7
BA187Y57
100
0 %
Level
V
Full
Volume
V
Empty
Table giving example
Point Measured
value
(mbar)
Level
(%)
Volume
(%)
1000
2 100 20 8
3 200 40 20
7 500 100 100
Note!
volume at x % level =
total volume volume (%)
10 0
6 Level Measurement Cerabar S