Ceraphant T PTC31, PTP31, PTP35 Installation
Endress+Hauser 7
3 Installation
3.1 Incoming acceptance, storage
• Incoming acceptance:
Check the packaging and the device for damage. Check that the goods delivered are complete
and nothing is missing.
•Storage:
Storage temperature -40...+85 °C (-40 to +185 °F)
3.2 Installation instructions
For typical possibilities for installing the Ceraphant T - see the diagram below:
• Pressure measurement in gases (left)
Mount Ceraphant T with shut-off assembly above the sampling nozzle so that any condensate
can drain off into the process.
• Pressure measurement in steam (centre)
Mount Ceraphant T with U-pipe above the sampling nozzle. Fill the U-pipe with fill fluid
before commissioning.
• Pressure measurement in liquids (right)
Mount Ceraphant T below or at the same level as the sampling nozzle.
P01-PTx3xxxx-11-xx-xx-xx-001
Fig. 2: Possibilities for installing to measure pressure in gases, steam and liquids.
➀ Ceraphant T
➁ Shut-off assembly
➂ U-pipe