Installation Ceraphant T PTC31, PTP31, PTP35
8 Endress+Hauser
3.2.1 Mounting instructions
Do not mount the device in the product flow or at a point where it could be affected by
pressure pulses
Calibration and functional testing are easier if the device is mounted downstream of a shut-off
assembly
The orientation of the Ceraphant T can result in zero point shift, i.e. in an unpressurised state,
the measured value does not display zero. This zero point shift can be corrected - see
"Operation" section
The on-site display can be rotated electronically 180° - see "Operation" section
The housing can be rotated up to 310°
Process connection G ½A, flush mounted, max. torque 40 Nm (29.5 lbf ft) (with PTP31)
3.3 Post-installation check
After installing the device, carry out the following checks:
Are all screws firmly tightened?