6.6 Seal for flange mounting
NOTICE
Distorted measurement results.
The seal is not allowed to press against the process isolating diaphragm as this could affect the
measurement result.
►
Ensure that the seal is not touching the process isolating diaphragm.
6.7 Installing the transmitter
The transmitter is installed with the mounting bracket supplied. The mounting bracket can be
installed on pipes with a diameter of 1¼" to 2" or on walls.
In the case of pipe mounting, the nuts on the bracket must be tightened uniformly with a torque
of at least 5 Nm (3.69 lbf ft).
6.7.1 Turning the display module
See Operating Instructions BA01044P on the CD-ROM supplied.
6.8 Post-installation check
m
Is the device undamaged (visual inspection)?
m
Does the device conform to the measuring point specifications?
For example:
• Process temperature
• Process pressure
• Ambient temperature
• Measuring range
m Are the measuring point identification and labeling correct (visual inspection)?