Commissioning Deltapilot M 4...20 mA HART
40 Endress+Hauser
Description
1 Perform "position adjustment". ä 37
A0030028
Fig. 10: Calibration with reference pressure –
wet calibration
A See Table, Step 8.
B See Table, Step 9.
A0017658
2 Select the "Level" measuring mode via the
"Measuring mode (005)" parameter.
Menu path: Setup Measuring mode
3 Select the "In pressure" level mode via the "Level
selection" parameter.
Menu path: Setup Extended setup Level
Level selection.
4 Select a pressure unit via the "Press eng. unit"
parameter, here "mbar" for example.
Menu path: Setup Press. eng. unit
5 Select a level unit via the "Unit before lin"
parameter, here "m" for example.
Menu path: Setup Extended setup Level
Unit before lin
6 Select the "Wet" option via the "Calibration mode"
parameter.
Menu path: Setup Extended setup Level
Calibration mode
7 If calibration is performed with a medium other
than the process medium, enter the density of the
calibration medium in the "Adjust density"
parameter.
Menu path: Setup Extended setup Level
Adjust density
8 The pressure for the lower calibration point is
present at the device, here 0 mbar for example.
Select the "Empty calib." parameter.
Menu path: Setup Extended setup Level
Empty calib.
Enter the level value, here 0 m for example. The
pressure value present is assigned to the lower level
value by confirming the value.