Deltapilot M 4...20 mA HART Commissioning
Endress+Hauser 49
8 Enter the height value for the lower calibration
point via the "Empty height" parameter, here 0.5 m
(1.6 ft) for example.
Menu path: Setup Extended setup Level
Empty height
A0031066
9 Enter the volume value for the upper calibration
point via the "Full calib." parameter, here 1000 liters
(264 US gal) for example.
Menu path: Setup Extended setup Level
Full calib.
10 Enter the height value for the upper calibration
point via the "Full height" parameter, here 4.5 m (15
ft) for example.
Menu path: Setup Extended setup Level
Full height
11 Enter the density of the medium via the "Adjust
density" parameter, here "1 g/cm
3
" (1 SGU) for
example.
Menu path: Setup Extended setup Level
Adjust density
12 Set the volume value for the lower current value (4
mA) via the "Set LRV" parameter.
Menu path: Setup Extended setup Current
output Set LRV
13 Set the volume value for the upper current value
(20 mA) via the "Set URV" parameter.
Menu path: Setup Extended setup Current
output Set URV
14 If the process uses a medium other than that on
which the calibration was based, the new density
has to be specified in the "Process density"
parameter.
Menu path: Setup Extended setup Level
Process density
Description
A
h
p
g
=
×r
h
p
g
=
×r
r=1
g
cm
3
B
D
CE
V
[l]
h
[m]
h
[m]
p
[mbar]
1000
4.5
0
0.5
0.5
50
4.5
450