Gammapilot M FMG60 XA00303F-G
Endress+Hauser 21
The safety screws at the pipe housing must not be loosened:
A0031759
When using the water cooling
To avoid damages at the detector or at the cooling jacket if the cooling water freezes: Empty cooling
jacket or protect against freezing.
Intrinsic safety
Observe the pertinent guidelines when interconnecting intrinsically safe circuits.
The intrinsically-safe input circuits are galvanically isolated from other circuits up to a peak value
of the nominal voltage of 375 V.
The intrinsically safe circuits of the device are isolated from ground and have a dielectric strength
of at least 500 V
rms
.
When the device is connected to an intrinsically safe circuit Ex ib, the type of protection changes to
Ex ib. Do not operate the temperature sensor in Zone 0 if the device is connected to an intrinsically
safe circuit of Category Ex ib.
When the device is connected to an intrinsically safe circuit Ex ic, the type of protection changes to
Ex ic. Do not operate the temperature sensor in Zone 0 or Zone 1 if the device is connected to an
intrinsically safe circuit of Category Ex ic.
Do not interconnect the 4...20 mA/HART signal circuits of the devices of a cascade set.
Increased safety (Ex eb)
Only use suitable certified Ex eb cable glands providing an ingress protection of at least IP66/67.
The cable glands must be suitable for the intended ambient temperature range.
Replace cable glands and sealing plugs only with identical parts.
Flameproof enclosure (Ex db)
Connect the device:
Using suitable cable and wire entries of protection type "Flameproof Enclosure (Ex db)".
Using piping systems of protection type "Flameproof Enclosure (Ex db)".
Seal unused entry glands with approved Ex db sealing plugs.
Safety instructions: Ex db joints
If required or if in doubt: ask manufacturer for specifications.
Potential equalization
Integrate the device into the local potential equalization.
Temperature tables
Temperature class
T6 or T5