Micropilot S FMR533 4 to 20 mA HART Mounting
Endress+Hauser 11
3.3.2 Engineering hints
Orientation
Recommended distance (1) wall - outer edge
of nozzle: ~1/6 of tank diameter
("Beam angle", ä 12).
Mount the Micropilot S at a position where
the tank movement due to filling/emptying of
the tank is of low influence.
Not in the centre (3), interference can cause
signal loss.
Not above the fill stream (4).
It is recommended to use a weather
protection cover (2) in order to protect the
transmitter from direct sun or rain. Assembly
and disassembly is simply done by means of a
tension clamp ("Accessories", ä 68).
L00-FMR533xx-17-00-00-yy-009
Tank installations
Avoid any installations (1), like limit
switches, temperature sensors, etc., inside the
signal beam (refer to beam angle
("Beam angle", ä 12).
It is essential that HiHi alarm is below the
blocking distance (BD) and the safety distance
(SD).
Symmetrical installations (2), e.g. vacuum
rings, heating coils, baffles, etc., can also
interfere with the measurement.
Optimization options
Antenna size: the bigger the antenna, the
smaller the beam angle, the less interference
echoes.
Mapping: the measurement can be optimized
by means of electronic suppression of
interference echoes.
Antenna alignment: "Optimum mounting
position", ä 16.
Stilling well: a stilling well can always be used
to avoid interference. The FMR532 with
planar antenna is recommended for stilling
wells with a diameter DN150 (6") and larger.
Metallic screens (3) mounted at a slope spread
the radar signals and can, therefore, reduce
interference echoes.
Please contact Endress+Hauser for further
information.
L00-FMR533xx-17-00-00-yy-010