Micropilot S FMR533 4 to 20 mA HART Operation
Endress+Hauser 37
5.5 HART communication
Apart from local operation, you can also parameterise the measuring device and view measured
values by means of a HART protocol. There are two options available for operation:
Operation via the universal handheld operating unit, the Field Communicator 375, 475.
Operation via the Personal Computer (PC) using the operating program
(e.g. FieldCare; Connections, ä 26).
Operation via the Tank Side Monitor NRF590.
!
Note!
The Micropilot S can also be operated locally using the keys. If operation is prevented by the keys
being locked locally, parameter entry via communication is not possible either.
5.5.1 Protocol specific data
5.5.2 Operation with Field Communicator 375, 475
All device functions can be adjusted via a menu operation with the Field Communicator 375, 475.
!
Note!
Further information on the handheld unit is given in the respective operating manual included in
the transport bag of the Field Communicator 375, 475.
Manufacturer ID 000011 hex
Device Type Code 0010 hex
Transmitter specific revision 03 hex
HART specification 5.0
DD-Files Information and files can be found on:
www.endress.com
www.hartcomm.org
Load HART Min. 250 Ω
Device variables Primary value: level or volume
1)
1) according to configuration
Features supported Burst mode
Additional Transmitter Status