Commissioning Micropilot S FMR533 4 to 20 mA HART
42 Endress+Hauser
"
Caution!
To successfully commission a precise measurement to the nearest mm, it is important you carry out
a history reset on first installation after mechanical installation and after the basic setup of the
device ( ä 50). Only after a history reset the mounting calibration is carried out. Enter the
measurement offset as the first point in the dip table for the mounting calibration. When a value is
dipped at a later date, make a second entry into the dip table, using the semi-automatic mode.
This way, you can easily carry out a linear correction of the measurement.
When configuring the function in "basic setup" (00) please take into account the following notes:
Select the functions as described, ä 28.
Some functions can only be used depending on the parameterisation of the device. For example,
the pipe diameter of a stilling well can only be entered if "stilling well" was selected beforehand
in the "tank shape" (002) function.
Certain functions (e.g. starting an interference echo mapping (053)) prompt you to confirm your
data entries. Press
O
or
S
to select "YES" and press
F
to confirm. The function is now started.
If you do not press a key during a configurable time period ( function group"display" (09)), an
automatic return is made to the home position (measured value display).
!
Note!
The device continues to measure while data entry is in progress, i.e. the current measured values
are output via the signal outputs in the normal way.
If the envelope curve mode is active on the display, the measured values are updated in a slower
cycle time. Thus, it is advisable to leave the envelope curve mode after the measuring point has
been optimised.
If the power supply fails, all preset and parameterised values remain safely stored in the EEPROM.
All functions are described in detail, as is the overview of the operating menu itself, in the manual
"BA00217F - Description of Instrument Functions", which can be found on the enclosed
CD-ROM.
The default values of the parameters are typed in boldface.