Micropilot S FMR533 4 to 20 mA HART Commissioning
Endress+Hauser 45
Function "process cond." (004)
This function is used to select the process conditions.
Selection:
standard
calm surface
turb. surface
agitator
fast change
heavy conditions
test:no filter
!
Note!
The phase evaluation of the Micropilot S ( ä 51) is only activated if you select the measuring
conditions "standard", "calm surface" or "heavy conditions". If, however, "heavy conditions"
is selected, no index values are stored. We strongly recommend that, in the case of rough product
surfaces or rapid filling, you activate the appropriate application parameters.
ENDRESS + HAUSER
E
+
standard calm surface
For all applications that do not fit into any of the following
groups.
Storage tanks with immersion tube or bottom filling
The filter and output damping are set to average values. The averaging filters and output damping are set to high
values.
steady meas. value
precise measurement
slower reaction time