Micropilot S FMR533 4 to 20 mA HART Commissioning
Endress+Hauser 53
Function "custody mode" (0A9)
This indicates the device calibration mode. The calibration mode (active) can be set using the
hardware security lock on the electronics ( ä 30).
Selection:
inactive
active pos.
active neg.
active pos.
The custody mode (device is lead-sealed and accurate to the nearest mm) is active and is held.
active neg.
Custody mode (device is lead-sealed and accurate to the nearest mm) is activated and not held, e.g.
because the signal-to-noise ratio is less than 5 dB (refer to function "echo quality" (056) in the
function group "extended calibr." (05)).
"
Caution!
After entering all the values and completing mounting and aligning work, enter the Reset Code
"555" in the function "reset" (0A3) to reset the device history for auto-correction or set history
reset to "yes" in order to reset the device history for the auto-correction.