TMT162 Commissioning
Endress+Hauser 29
6.4.2 Supported HART
®
commands
r = read access, w = write access
Output
simulation
Activate simulation mode.
Input:
OFF
•ON
++V9H7
Simulation
value
Input of the simulation value (current).
Input: 3.58 to 23 mA as of SW version 01.03.00.
To SW version 01.03.00 21.7 mA.
++V9H8
User
calibration
(trim) analog
output
For changing the 4 or 20 mA value by ± 0.150 mA
Trimming 4 mA
Trimming 20 mA
SW 01.03.00 SW 01.03.00 -
Function group SERVICE FUNCTIONS
Available in ReadWin
®
2000, HART
®
handheld module DXR 275/375 (Symbol
7
),
Commuwin II with Matrix address
ReadWin
®
2000
7
/FieldCare CW II-
Matrix
Function group MEASURED VALUES
Available in ReadWin
®
2000, HART
®
handheld module DXR275/375 (Symbol
7
),
Commuwin II with Matrix address
ReadWin
®
2000
7
/FieldCare CW II-
Matrix
PV PV value + + V0H0
AO PV value in mA - + V0H1
PV % PV value in % - + V0H2
Sensor 1 Sensor 1 process value - + V0H3
Sensor 2 Sensor 2 process value - + V0H5
Internal
temperature
(RJ value)
Internal temperature of the device (RJ value) - + V0H7
No. Description Access
Universal Commands
00 Read unique identifier r
01 Read primary variable r
02 Read p.v. current and percent of range r
03 Read dynamic variables and p.v. current r
06 Write polling address w
11 Read unique identifier associated with tag r
12 Read message r

Other manuals for Endress+Hauser iTEMP HART TMT162