Installation iTEMP TMT71, TMT72
12 Endress+Hauser
100 (3.94)
12.5 (0.49)
H
116 (4.57)
A0039296
H The height of housing H varies depending on the terminal version: screw terminals =
114 mm (4.49 in), push-in terminals = 111.5 mm (4.39 in)
4.1.2 Mounting location
• Head transmitter:
• In the terminal head, flat face, as per DIN EN 50446, direct mounting on insert with cable
entry (middle hole 7 mm)
• In the field housing, separated from the process
• With DIN rail clip on DIN rail as per IEC 60715, TH35
• DIN rail transmitter:
In DIN rail housing on DIN rail as per IEC 60715, TH35
NOTICE
When using DIN rail transmitters with a thermocouple/mV measurement, increased
measurement deviations may occur depending on the installation situation and ambient
conditions.
‣
If the DIN rail transmitter is mounted on the DIN rail without any adjacent devices, this
may result in deviations of up to ± 1.34 °C. If the DIN rail transmitter is mounted in series
between other DIN rail devices (reference operating conditions: 24 V, 12 mA), deviations
of up to + 2.94 °C may occur.