Mounting Levelflex FMP53 FOUNDATION Fieldbus
12 Endress+Hauser
6 Mounting
6.1 Mounting requirements
6.1.1 Suitable mounting position
A
1 2
C
B
3
A0014130
 3 Mounting requirements for Levelflex
Mounting distances
Distance (A) between wall and rod probe:
for smooth metallic walls: > 50 mm (2 in)
for plastic walls: > 300 mm (12 in) to metallic parts outside the vessel
Distance (B) between rod probe and internal fittings (3) in the vessel: > 300 mm (12 in)
When using more than one Levelflex:
Minimum distance between the sensor axes: 100 mm (3.94 in)
Distance (C) from end of probe to bottom of the vessel: > 10 mm (0.4 in).