Integration into a FOUNDATION Fieldbus network Levelflex FMP53 FOUNDATION Fieldbus
28 Endress+Hauser
8.4.2 Block configuration when device is delivered
DIAGNOSTIC
PID ARITHMETIC SIGNAL_CHAR
S
RESOURCE
ANALOG_INPUT_1
ANALOG_INPUT_2
DI
ADV_SETUP
DATA_TRANSFER
EXPERT_INFO
SERVICE_INFO
DISPLAY
INPUT_SELECTOR
INTEGRATOR ANALOG_ALARM
EXPERT_CONFIG
SETUP
SERVICE_SENSOR
PV
SV
ESC
OPEN
OPEN
E
Device_01 F
mm
4841.000
A0017217
 7 Block configuration when device is delivered
S Sensor
PV Primary value: Level linearized
SV Secondary value: Distance
8.5 Assignment of the measured values (CHANNEL) in an AI Block
The input value of an Analog Input Block is defined by the CHANNEL parameter.
Channel Measured value
0 Uninitialized
89 Measured capacitance
144 EOP shift
145 Interface distance
172 Calculated DC value
211 Terminal voltage
212 Sensor debug
32785 Absolute EOP amplitude